Specifications

EPL 

 Lever Type (lever feedback)

 Single

Double 

  Input Signal

4 ~ 20 mA DC (Note. 1)

  Input Resistance

235 +/-15 (4...20 mA DC)

  Supply Air Pressure

1.4 ~ 7 kgf/cm2

  Stroke

10 ~ 80 mm

  Air piping connection

PT 1/4 or NPT 1/4

  Conduit Connection

PF 1/2

  Explosion Proof Classification

Ex md IIB T6 (Note. 2)

  Ambient Temperature

- 20 C ~ 70 C

  Material

Aluminium Diecast Body

  Weight

with Terminal Box 2.9kg

 Note : 1) SPLIT Range adjustment is also available (4-12, 12-20mA DC)
           2) The explosion-proof type is only available for standard (Certified No.99-1075-Q1)
 

Characteristics and Performance 

Performance

Lever Type

Linearity

Within +/-1.0% F.S

Sensitivity

Within +/-1.0% F.S

Hysteresis

Within +/-0.1% F.S

Repeatability

Within +/-1.0% F.S

Air Consumption

5 LPM (Sup/ 1.4 kgf / cm2)

Flow Capacity

80 LPM (Sup/ 1.4 kgf / cm)


AIR PIPING (For model EPL)

Direct Acting (DA)

Reverse Acting (RA)

Increasing input signal,
Stem lift downward.
Actuator : DA
Connection : out 1

Increasing input signal,
Stem lift upward.
Actuator : RA
Connection : out 2

Increasing input signal,
Stem lift downward.
Actuator : DA
Connection : out 2

Increasing input signal,
Stem lift upward.
Actuator : RA
Connection : out 1

Increasing input signal,
Stem lift downward.

Increasing input signal,
Stem lift upward.

         

INSTALLATION

SERIES : EPL (LINEAR TYPE)

As shown the installation diagram, this control valve should be easily mounted using bolts without bracket. Firmly fixed through mounting holes on the side of the positioner type EPL
In case of using bracket, this units are available for following methods;

- L - type bracket

1004526installation_1s.gif (876 bytes)

- Single spring actuator

When the signal current apply for 50 %(ie, 12mA), the position of feed back lever should be located in right angle (90deg.) to the stem of valve. The left figure is the configuration viewed from front side.

The stroke range for performance is 10 to 80 mm and operating angle of feedback lever should be at least 10degree and at most 30degree to achieve specified accuracy and linearity

  EPL - LINEAR TYPE